Fluke 435-II
Catalog #: 4116661
Three-Phase Power Quality and Energy Analyzer
- Overview
- Specifications
- Summary
- Cases
- Accessories
- Current Clamps/Probes
Discontinued and replaced with Fluke 1775
Product Highlights
- Troubleshoot real-time: Analyze the trends using the cursors and zoom tools.
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
- Power inverter efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
- PowerWave data capture: 435 and 437 Series II analyzers capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.).
- Waveform capture: 435 and 437 Series II models capture 100/120 cycles (50/60Hz) of each event that is detected in all modes, without set-up.
- Automatic Transient Mode: 435 and 437 Series II analyzers capture 200 kHz waveform data on all phases simultaneously up to 6 kV.
- Energy loss calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint true system energy losses in dollars (other local currencies available).
- Fully Class-A compliant: 435 and 437 Series II analyzers conduct tests according to the stringent international IEC 61000-4-30 Class-A standard.
- 400 Hz measurement: 437 Series II analyzer captures power quality measurements for avionic and military power systems.
- Measure all three phases and neutral: With included four flexible current probes with enhanced thin flex designed to fit into the tightest places.
- Automatic Trending: Every measurement is always automatically recorded, without any set-up.
- System-Monitor: Ten power quality parameters on one screen according to EN50160 power quality standard.
- Logger function: Configure for any test condition with memory for up to 600 parameters at user defined intervals.
- View graphs and generate reports: With included analysis software.
- Battery life: Seven hours operating time per charge on Li-ion battery pack.
- Mains signaling: 435 and 437 Series II analyzers measure interference from ripple control signals at specific frequencies.
Each Unit Includes
- BC430 Power Adapter
- International plug adapter set
- BP290 (Single capacity Li-ion battery) 28Wh (7 hours or more)
- TL430 Test lead and Alligator clip set
- WC100 color coding clips and regional decals
- i430flex-TF, 24 inch (61cm) length, 4 clamps
- 8 GB SD card
- PowerLog on CD (includes operator manuals in PDF format)
- USB cable A-Bmini
- C1740 Soft Case
- ISO 9001 - Statement of Calibration Practices (W/Data)
Technical Data |
Voltage inputs |
Number of inputs |
4 (3 phase + neutral) dc-coupled |
Maximum input voltage |
1000 Vrms |
Nominal voltage range |
Selectable 1 V to 1000 V |
Max. peak measurement voltage |
6 kV (transient mode only) |
Input impedance |
4 MΩ//5 pF |
Bandwidth |
> 10 kHz, up to 100 kHz for transient mode |
Scaling |
1:1, 10:1, 100:1, 1,000:1 10,000:1 and variable |
Current inputs |
Number of inputs |
4 (3 phase + neutral) dc- or ac-coupled |
Type |
Clamp or current transformer with mV output or i430flex-TF |
Range |
0.5 Arms to 600 Arms with included i430flex-TF (with sensitivity 10x)
5 Arms to 6000 Arms with included i430flex-TF (with sensitivity 1x)
0.1 mV/A to 1 V/A and custom for use with optional ac or dc clamps |
Input impedance |
1 MΩ |
Bandwidth |
> 10 kHz |
Scaling |
1:1, 10:1, 100:1, 1,000:1 10,000:1 and variable |
Sampling system |
Resolution |
16 bit analog to digital converter on 8 channels |
Maximum sampling speed |
200 kS/s on each channel simultaneously |
RMS sampling |
5000 samples on 10/12 cycles according to IEC61000-4-30 |
PLL synchronization |
4096 samples on 10/12 cycles according to IEC61000-4-7 |
Nominal frequency |
434-II and 435-II: 50 Hz and 60 Hz
437-II: 50 Hz, 60 Hz and 400 Hz |
Display modes |
Waveform display |
Available in all modes via SCOPE key
435-II and 437-II: Default display mode for Transients function
Update rate 5x per second
Displays 4 cycles of waveform data on screen, up to 4 waveforms simultaneously |
Phasor diagram |
Available in all modes via Scope waveform display
Default view for Unbalance mode |
Meter readings |
Available in all modes except Monitor and Transients, provides tabulated view of all available readings
Fully customizable up to 150 readings for Logger mode |
Trend graph |
Available in all modes except Transients
Single vertical cursor with min max and avg reading at cursor position |
Bar graph |
Provides 50/60** cycles of waveform information and associated 1/2 cycle rms values for Volts and Amps |
Measurement modes |
Scope |
4 voltage waveforms, 4 current waveforms, Vrms, Vfund. Arms, A fund, V @ cursor, A @ cursor, phase angles |
Volts/amps/hertz |
Vrms phase to phase, Vrms phase to neutral, Vpeak, V Crest Factor, Arms Apeak, A Crest Factor, Hz |
Dips and swells |
Vrms½, Arms½, Pinst with programmable threshold levels for event detection |
Harmonics dc, 1 to 50, up to 9th harmonic for 400 Hz |
Harmonics Volts, THD, Harmonic Amps, K factor Amps, Harmonic Watts, THd Watts, K factor Watts, Interharmonic
Volts, Interharmonic Amps, Vrms, Arms (relative to fundamental or to total rms) |
Power and energy |
Vrms, Arms, Wfull, Wfund., VAfull, VAfund., VAharmonics, VAunbalance, var, PF, DPF, CosQ, Efficiency factor, Wforward, Wreverse |
Energy loss calculator |
Wfund, VAharmonics, VAunbalance, var, A, Loss Active, Loss Reactive, Loss Harmonics, Loss Unbalance, Loss Neutral, Loss Cost (based upon user defined cost / kWh) |
Inverter efficiency (requires optional dc current clamp) |
Wfull, Wfund, Wdc, Efficiency, Vdc, Adc, Vrms, Arms, Hz |
Unbalance |
Vneg%, Vzero%, Aneg%, Azero%, Vfund, Afund, V phase angles, A phase angles |
Inrush |
Inrush current, Inrush duration, Arms½, Vrms½ |
Monitor |
Vrms, Arms, harmonic Volts, THD Volts, PLT, Vrms½, Arms½, Hz, dips, swells, interruptions, rapid voltage changes, unbalance and mains signalling.
All parameters are measured simultaneously in accordance with EN50160 Flagging is applied according to IEC61000-4-30 to indicate unreliable readings due to dips or swells |
Flicker (435-II and 437-II only) |
Pst(1min), Pst, Plt, Pinst, Vrms ½, Arms ½, Hz |
Transients (435-II and 437-II only) |
Transient waveforms 4x Voltage 4x Amps, triggers: Vrms ½, Arms ½, Pinst |
Mains Signaling (435-II and 437-II only) |
Relative signaling voltage and absolute signaling voltage averaged over three seconds for up to two selectable signaling frequencies |
Power Wave (435-II and 437-II only) |
Vrms½, Arms½ W, Hz and scope waveforms for voltage amps and watts |
Logger |
Custom selection of up to 150 PQ parameters measured simultaneously on 4 phases |
General specifications |
Case |
Design Rugged, shock proof with integrated protective holster
Drip and dust proof IP51 according to IEC60529 when used in tilt stand position
Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 |
Display |
Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power
Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD
Resolution: 320 x 240 pixels
Contrast and brightness: user-adjustable, temperature compensated |
Memory |
8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally
Screen save and multiple data memories for storing data including recordings (dependent on memory size) |
Real-time clock |
Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Environmental |
Operating temperature |
0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery |
Storage temperature |
-20 °C ~ +60 °C |
Humidity |
+10 °C ~ +30 °C: 95 % RH non-condensing
+30 °C ~ +40 °C: 75 % RH non-condensing
+40 °C ~ +50 °C: 45 % RH non-condensing |
Maximum operating altitude |
Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft) |
Electro-Magnetic-Compatibility (EMC) |
EN 61326 (2005-12) for emission and immunity |
Interfaces |
mini-USB-B, Isolated USB port for PC connectivity
SD card slot accessible behind instrument battery |
Warranty |
Three years (parts and labor) on main instrument, one year on accessories |
Phase angle Measurement range: |
-360° … +360° |
Included accessories |
Power options |
BC430 Power Adapter
International plug adapter set
BP290 (Single capacity Li-ion battery) 28Wh (7 hours or more) |
Leads |
TL430 Test lead and Alligator clip set |
Color coding |
WC100 color coding clips and regional decals |
Flexible current probes |
i430flex-TF, 24 inch (61cm) length, 4 clamps |
Memory, Software and PC connection |
8 GB SD card
PowerLog on CD (includes operator manuals in PDF format)
USB cable A-Bmini |
Carrying case |
C1740 Soft Case for 434-II and 435-II
C437 Hard Case with rollers for 437-II |
Type (Power Quality) |
3 Phase, Single Phase |
Maximum Current AC |
6000 A |
Maximum Voltage AC |
1000 V |
True Power / Work ( W) |
Yes |
Apparent Power (VA) |
Yes |
Reactive Power (VAR) |
Yes |
Current Input Channels |
4 |
Voltage Input Channels |
4 |
Measurement Frequency (Power Quality) |
50 Hz, 60 Hz |
Display (Power Quality) |
Digital, Graphical, Oscilloscope |
Alarms |
Yes |
Transient Capture |
Yes |
Minimum Transient Duration |
micro-seconds |
Displays Waveform |
Yes |
Energy |
Yes |
Phasor Diagrams |
Yes |
Power Factor (Power Quality) |
Yes |
Harmonics |
Yes |
Maximum Harmonics Range |
50 |
Current Clamps Included |
Yes |
Class A Compliant |
Yes |
Crest Factor |
Yes |
CAT Rating |
IV |
CAT Voltage Rating (V) |
1000V, 600V |
GPS Location |
Yes |
|
Unique Features |
Power Inverter Efficiency: Simultaneously measure AC output power and DC input power for power electronics systems using optional DC clamp.
PowerWave Data Capture: Capture fast RMS data, show half-cycle and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.).
Energy Loss Calculator: Classic active and reactive power measurements, unbalance and harmonic power, are quantified to pinpoint the fiscal costs of energy losses.
Troubleshoot Real-Time: Analyze the trends using the cursors and zoom tools.
Highest Safety Rating in the Industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
Measure All Three Phases and Neutral: With included four flexible current probes with enhanced thin flex design to fit into the tightest places.
Automatic Trending: Every measurement is always automatically recorded, without any set-up. |
Warranty |
3 YEARS |
Warranty Details |
Three years (parts and labor) on main instrument, one year on accessories |
Calibration Included |
None |
Power Supply Voltage |
120V/220V Universal, Battery Powered |
Data Logging |
Yes |
Interfaces I/O |
USB |
Storage |
SD Card |
IP Rating |
IP51 |
Product Weight |
16.36 LBS |
Product Height |
13.19 IN |
Product Length |
15.47 IN |
Product Width |
12.24 IN |
Shipping Weight |
18 LBS |
Country of Origin |
Romania |
Shipping Height |
13.19 IN |
Shipping Length |
15.47 IN |
Shipping Width |
12.24 IN |
UPC |
095969615563 |
|
Cases
Product |
Price |
|
Fluke C437-II
Catalog #: 4116743
Hard Rolling Case with Rollers
|
$1,110.24
|
Accessories
Product |
Price |
|
Fluke 430-II/MA
Catalog #: 4779032
Motor Analyzer Upgrade Kit
|
$3,722.24
|
|
Fluke AC285
Catalog #: 1610159
SureGrip Alligator Clips
|
$60.24
|
|
Fluke BP290
Catalog #: 4025762
Li-Ion Single Capacity Battery Pack for Fluke 190-Series II ScopeMeter Test Tool
|
$331.24
|
|
Fluke BP291
Catalog #: 3894688
Li-Ion Double Capacity Battery Pack
|
$463.24
|
|
Fluke EBC290
Catalog #: 3894906
External Battery Charger
|
$174.24
|
Current Clamps/Probes
|