AEMC MN291
Catalog #: 2115.84
AC Current Probe Model MN291 (Lead - 100mVDC/A - 240A max)
- Overview
- Specifications
- Summary
- Accessories
Product Highlights
- Small, compact size
- Measurement range of 0.5 to 240AAC
- Large jaw opening accommodates conductors up to 250MCM
- Designed for DMMs, loggers, recorders and oscilloscopes
- 40Hz to 10kHz response
- 100mVDC/AAC output signals
- Conforms to EN 61010, 600V Cat. III safety standard
- CE Mark
- UL approved
Applications
- Measuring in breaker panels
- Industrial loads
- HVAC
- Residential and commercial sites
- Data logging/recording
Operating Range |
Current Range |
0.5 to 200A |
Frequency Range |
40 to 10kHz |
Limit Operating Conditions |
200A permanently to 1kHz; Derating above 3kHz: 200A x (1/0.333 F), F in kHz |
Common Mode Voltage |
600VAC |
Crest Factor |
3 @ 200Arms with an error (due to CF) of 4% |
Current Overload |
240A for 10 min |
Reference Conditions |
20° to 26°C, 20 to 75% RH, 48 to 65Hz, external magnetic field <40A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered. Load impedance 1MW |
Working Voltage |
600VAC |
Influence of Adjacent Conductor |
Range Value |
50Hz |
Influence of Adjacent Conductor |
< 15mA/A |
Influence of Conductor Position |
Influence of Conductor Position |
0.5% of Reading @ 50/60Hz |
Influence of Humidity |
Influence of Humidity |
15 - 90% RH: £0.2% of mV output per 10°K @ 18°C to 28°C |
Output Signal |
Output Signal |
100mV DC/AAC |
Mechanical Specifications |
Altitude |
Operating: 0 to 2000m; Non-operating: 0 to 12km |
Colors |
Dark gray handles with red cover |
Dimensions |
5.47 x 2.00 x 1.18" (139 x 51 x 30mm) |
Drop Test |
Test per IEC 68-2-32: 1.0 m drop on 38 mm of Oak on concrete |
Jaw Opening |
.84" (21mm) |
Material |
Jaws: Polycarbonate with 10% fiberglass charge, Red UL 94 V0; Case: Polycarbonate |
Maximum Bus Bar Size |
0.78 x 0.19" (20 x 5mm) |
Maximum Cable Diameter |
One 0.78" & Oslash; (20mm) |
Mechanical Shock |
100g per IEC 68-2-27 |
Operating Temperature |
14° to 131°F (-10° to 55°C) |
Operating Relative Humidity |
10° to 35°C 85% RH (without roll-off above 35°C) |
Output |
Double reinforced insulated 5ft. (1.5m) lead with safety 4mm banana plug |
Protection Index (IP) |
IP 40 (IEC 529) |
Impact Test |
IK04 0.5 J EN50102 |
Storage Temperature |
-40° to 158°F (-40° to 70°C) |
Vibration |
Test per IEC 68-2-6 |
Weight |
6.5 oz (180g) |
External Influences |
Influence of Temperature |
£150 ppm/°K, or 0.15% of mV output per 10K° |
Safety Reference Specifications |
Safety Ratings |
EN 61010-2-32 |
Agency Approvals |
CE Mark |
Clamp Meters/Current Clamp Adaptors / Current Clamps Template |
Type (Current Clamp Adaptors |
CT |
Maximum Current |
240 A |
Current Output |
No |
Voltage Output |
Yes |
AC Current Only |
Yes |
AC/DC Current |
No |
Current Accuracy |
2% |
Maximum Conductor Size Fixed |
0.78 IN |
CAT Rating |
III |
CAT Voltage Rating (V) |
600V |
Connector |
Banana |
Style (Current Clamps) |
Fixed |
Battery Powered |
No |
Externally Powered |
No |
Data Logging |
No |
Unique Features |
Max size conductor 0.78
DC output signal 100mVDC/AAC |
Warranty |
12 MONTHS (1 YEARS) |
Calibration Included |
Factory Calibration |
IP Rating |
IP40 |
Product Weight |
6.5 OUNCES (0.4062 LBS) |
Shipping Weight |
3 LBS |
ECCN Number |
EAR99 |
HTS/Schedule B Number |
9030908060 |
Country of Origin |
United States |
UPC |
865338030136 |
|
Accessories
Product |
Price |
|
AEMC 2133.73
Catalog #: 2133.73
Bag Extra Large Classic Tool Bag (Replacement for Models 3945/3945-B, 6240, 6250, 6471, 6505, 5050, 5060, 5070, 8333, 8335, 8336 and PEL 105)
|
$100.23
|
|
AEMC 2152.24
Catalog #: 2152.24
Lead Set of 2, Color-coded (red/black) 5 ft Safety Leads {Rated 1000V CAT IV}
|
$24.21
|
|
|
|