| Operating Range | 
        
            | Current Range | 0.5 to 200A | 
        
            | Frequency Range | 40 to 10kHz | 
        
            | Limit Operating Conditions | 200A permanently to 1kHz; Derating above 3kHz: 200A x (1/0.333 F), F in kHz | 
        
            | Common Mode Voltage | 600Vrms | 
        
            | Crest Factor | 3 @ 200Arms with an error (due to CF) of 4% | 
        
            | Current Overload | 240A for 10 min | 
        
            | Current Overload | 
        
            | Range Value | null | 
        
            | Overload | 240A for 10 min ON, 30 min OFF | 
        
            | Reference Conditions | 20° to 26°C, 20 to 75% RH, 48 to 65Hz, external magnetic field <40A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered, load impedance 1MW | 
        
            | Working Voltage | 600VAC | 
        
            | Influence of Adjacent Conductor | 
        
            | Range Value | 50Hz | 
        
            | Influence of Adjacent Conductor | < 15mA/A | 
        
            | Influence of Conductor Position | 
        
            | Influence of Conductor Position | 0.5% of Reading @ 50/60Hz | 
        
            | Influence of Frequency | 
        
            | Range Value | 40Hz to 1kHz / 1 to 10kHz | 
        
            | Influence of Frequency | 3% of mV output / 12% of mV output | 
        
            | Influence of Humidity | 
        
            | Influence of Humidity | 10 - 90% RH: £0.2% of mV output per 10°K @ 18°C to 28°C | 
        
            | Influence of Load | 
        
            | Range Value | 40Hz to 1kHz / 1 to 10 kHz | 
        
            | Influence of Load | <3% of mA output / <12% of mA output | 
        
            | Output Signal | 
        
            | Output Signal | 10mV/A | 
        
            | Mechanical Specifications | 
        
            | Altitude | Operating: 0 to 2000m; Non-operating: 0 to 12km | 
        
            | Colors | Dark gray handles with red cover | 
        
            | Dimensions | 5.47 x 2.00 x 1.18" (139 x 51 x 30mm) | 
        
            | Drop Test | Test per IEC 68-2-32: 1.0 m drop on 38 mm of Oak on concrete | 
        
            | Jaw Opening | .84" (21mm) | 
        
            | Material | Jaws: Polycarbonate with 10% fiberglass charge, Red UL 94 V0; Case: Polycarbonate | 
        
            | Maximum Bus Bar Size | 0.78 x 0.19" (20 x 5mm) | 
        
            | Maximum Cable Diameter | One 0.78" & Oslash; (20mm) | 
        
            | Mechanical Shock | 100g per IEC 68-2-27 | 
        
            | Operating Temperature | 14° to 131°F (-10° to 55°C) | 
        
            | Operating Relative Humidity | 10° to 35°C 85% RH (without roll-off above 35°C) | 
        
            | Output | Double reinforced insulated 5 ft (1.5m) lead with safety 4mm banana plug | 
        
            | Protection Index (IP) | IP 40 (IEC 529) | 
        
            | Impact Test | IK04 0.5 J EN50102 | 
        
            | Storage Temperature | -40° to 158°F (-40° to 70°C) | 
        
            | Vibration | Test per IEC 68-2-6 | 
        
            | Weight | 6.5 oz (180g) | 
        
            | External Influences | 
        
            | Influence of Temperature | £150 ppm/°K, or 0.15% of mA output per 10K° | 
        
            | Safety Reference Specifications | 
        
            | Safety Ratings | EN 61010-2-32 | 
        
            | Agency Approvals | CE Mark |