Megger MTO106
Catalog #: MTO106
2-Channel Transformer Ohmmeter with 10m Kelvin Lead Set, 1 mA - 6 A, 48 VDC
- Overview
- Specifications
- Summary
Product Highlights
- Performs safe and accurate field measurement of winding resistance
- Designed for smaller transmission and distribution transformers
- 2 channels with max 6 A current output
- ±0.25% measurement accuracy
- 48 V test voltage for fast saturation of transformers
- Adjustable output current enables user to select from five current ranges
- Multimeter type operation is intuitive and fast
- Minimal number of controls — single selector switch for test current, single button to activate test cycle
- Safety ensured through automatic, passive discharge circuitry
- Continuous operation with very short start-up time
- Compact size and low weight for true portability
- Rugged plastic case rated to IP67 when closed
- Test leads fitted with Kelvin clamps for single, one-time connection to unit under test
- 33 ft. test lead length allows easy testing of pole mounted transformers
Applications:
- Field measurements of smaller transmission and distribution transformers:
- To verify factory test readings
- As part of a regular maintenance program
- To help locate the presence of defects in transformers
- For general resistance measurements, including:
- Control wiring
- Voltage regulators
- Motors
- Generators
Each Unit Includes
- 1 - MTO106 Transformer Ohmmeter
- 1 - Test Lead with Banana Connector and Kelvin Clamp, 10 m (33 ft), Black (GC-32310)
- 1 - Test Lead with Banana Connector and Kelvin Clamp, 10 m (33 ft), Red (GC-32312)
- 1 - Ground Lead, 5 m (16 ft) 2.5 mm² (GA-00200)
- 1 - Mains Cable (AA-00010)
- 1 - User's Manual
- 1 - Report Pad
- 1 - Reporting Template File
- 1 - Cable Carry Bag (2000-091)
General Specifications |
Environment |
Application field |
The instrument is intended for use in high-voltage substations and industrial environments. |
Temperature |
Operating |
-20°C to +50°C (-4°F to +122°F) |
Storage & transport |
-50°C to +70°C (-58°F to +158°F) |
Humidity (operating) |
0% – 90% RH, non-condensing |
CE-marking |
LVD |
2014/35/EU |
EMC |
2014/30/EU |
RoHS |
2011/65/E U |
General |
Mains voltage |
100 - 240VAC, 50/60Hz |
Input power |
400 VA (max) |
Case |
Ruggedized plastic case with removable lid and carrying handle, IP 67 when closed |
Dimensions (W x D x H) |
360 x 304 x 194 mm (14.2 x 12 x 7.6 in.) |
Weight |
7.3 kg (16 lbs) excl. cables |
Display |
4-inch, backlit, monochrome alphanumerical display |
Test leads |
2 x 10 m (33 ft), with banana connectors and Kelvin clamps |
Ground lead |
1 x 5 m (16 ft), 2.5 mm² |
Measurement section |
Measurment range |
10 μOhm to 30 kOhm |
Resolution |
Up to 4 digits |
Open circuit test voltage |
up to 48 V DC |
Measurement voltage |
up to 20 V DC |
Product Height |
7.6 IN |
Product Length |
12 IN |
Product Width |
14.2 IN |
Country of Origin |
Sweden |
|
|
|
|