| AC current | 
        
            | Range | Resolution | Accuracy | Frequency Response | Overload Protection | 
        
            | 400 A 1000 A
 1500 A
 400 A
 1000 A
 1500 A
 | 0.1 A 1 A
 1 A
 0.1 A
 1 A
 1 A
 | ±(1.5% reading + 5 digits)* ±(1.9% reading + 7 digits)
 ±(2.5% reading + 7 digits)
 ±(1.9% reading + 5 digits)*
 ±(2.5% reading + 7 digits)
 ±(3.0% reading + 7 digits)
 | 50 Hz ~ 60 Hz 50 Hz ~ 60 Hz
 50 Hz ~ 60 Hz
 61Hz ~ 400 Hz
 61 Hz ~ 200Hz
 61 Hz ~ 200 Hz
 | 1500 A rms 1500 A rms
 1500 A rms
 1500 A rms
 1500 A rms
 1500 A rms
 | 
        
            | AC Conversion Type | * add 2 digits to accuracy when reading less 15% of full scale. AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies
 are given for sine wave at full scale and non-sine wave below half scale. For non-sine wave add the following Crest
 Factor corrections:
 For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
 For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
 For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
 | 
        
            | Max.CF | 2 @ 600A 1.5 @ 1500A
 | 
        
            | DC current | 
        
            | Range | Resolution | Accuracy | Over voltage protection | 
        
            | 400 A 1000 A
 1500 A
 Position Error: Add
 | 0.1 A 1 A
 1 A
 ±1% of LCD reading
 | ±(1.0% reading + 3 digits) ±(1.9% reading + 7 digits)
 ±(2.5% reading + 7 digits)
 | AC 1000 A for 1 min AC 1000 A for 1 min
 AC 1000 A for 1 min
 | 
        
            | AC voltage (auto-ranging) | 
        
            | Range | Resolution | Accuracy | Over voltage protection | 
        
            | 400 V 750 V
 | 100 mV 1 V
 | ±(1.0% reading + 5 digits) 50 Hz ~ 500 Hz*
 ±(1.0% reading + 5 digits)
 50 Hz ~ 500 Hz*
 (* add 2 digits to accuracy when reading less 15% of full scale.)
 | 750 V rms 750 V rms
 | 
        
            | Input Impedance | ≥1 MΩ// less than 100pF | 
        
            | AC Conversion Type | AC Conversions are ac-coupled, true rms responding, calibrated to the rms value of a sine wave input. Accuracies are given for sine wave at full scale and non-sine wave below half scale.
 For non-sine wave add the following Crest Factor corrections:
 For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy.
 For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy.
 For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
 Max.CF: 2 @ 600V, 1.5 @ 750V
 | 
        
            | DC voltage (auto-ranging) | 
        
            | Range | Resolution | Accuracy | Over voltage protection | 
        
            | 400 V 1000 V
 | 100 mV 1 V
 | ±(0.7% reading + 2 digits) ±(0.7% reading + 2 digits)
 | 1000 V rms 1000 V rms
 | 
        
            | Input impedance | ≥ 1 MΩ | 
        
            | Resistance and continuity | 
        
            | Range | Resolution | Accuracy | Over voltage protection | 
        
            | 0 – 400 Ω | 100 mΩ | ±(1.0% reading + 3 digits) | 600 V rms | 
        
            | Continuity check | Buzzer sounds when resistance< 30 Ω | 
        
            | Frequency | 
        
            | Range | Resolution | Accuracy | Over voltage protection | 
        
            | 20 – 400 Hz | 1 Hz | ±(0.1% reading + 2 digits) | AC /DC 1000 A for 1 min | 
        
            | Sensitivity | 3 A rms for < 400 Hz | 
        
            | Peak Hold | ±(3% reading +10 digits) * >750 V Unspecified.
 * >800 A Unspecified.
 | 
        
            | Min/Max Hold | Add ± 15 dgt to accuracy for ACA and DCA. | 
        
            | LCD | Display: 3 3/4 digit large scale readout Count: 4000
 Overrange: “OL”
 | 
        
            | Power supply | 1 x PP3 MN1604 6LR61 alkaline cell Battery life: 100 hours
 | 
        
            | Operating temperature range and humidity | 0 °C - 30 °C (≤ 80% RH) 30 °C - 40 °C (≤ 75% RH)
 40 °C - 50 °C (≤ 45% RH)
 | 
        
            | Conductor size | Maximum conductor size: 51 mm | 
        
            | Safety | IEC61010-1 CAT IV 600 V For use on uninsulated conductors
 | 
        
            | EMC | EN61326-1 | 
        
            | Pollution degree | 2 | 
        
            | Storage temperature range | -20°C - + 60°C 0 to 80% RH (Battery removed) | 
        
            | Dimensions | 105 mm (W) x 275 mm (L) x 48 (H) | 
        
            | Weight | 524 g including battery |