AEMC SR661
Catalog #: 2113.49
AC Current Probe Model SR661 (BNC - 100mV/A-10A;10mV/A-100A;1mV/A-1000A max)
- Overview
- Specifications
- Summary
- Accessories
Product Highlights
- Measurement range of 100mA to 2000AAC
- Large jaw opening accommodates conductors up to two 500MCM conductors
- Ergonomic design and easy operation
- Conforms to EN 61010, 600V Cat. III safety standard
- Low phase shift for power measurements
- Available with mA or mV output signals
- Designed for DMMs, recorders, loggers, oscilloscopes, power and harmonic meters
- CE Mark
Applications
- Power quality measuring
- Low industrial loads
- Measuring around cable bundles
- Power load monitoring
- Waveform analysis
| Operating Range |
| Current Range |
100mA to 1200 Arms (2000A peak) |
| Frequency Range |
1Hz to 100kHz (@ -3dB) See typical response curves |
| Common Mode Voltage |
600VAC |
| Crest Factor |
£6 |
| Current Overload |
1200A for 40 min ON, 20 min OFF |
| Current Overload |
| Range Value |
1mV/A (1V at 1000A), 10mV/A (1V at 100A), 100mV/A (1V at 10Arms) |
| Overload |
1200A for 40 min ON, 20 min OFF duty cycle, 20A continuous 12A continuous |
| Load Impedance |
1MW @ 47pF |
| Open Secondary Voltage |
< 25V by limiting circuit |
| Reference Conditions |
23°C ±3°K, 20 to 75% RH, 48 to 65Hz, external magnetic field <40A/m, no DC component, no external current carrying conductor, test sample centered. Load impedance 1MW/47pF |
| Working Voltage |
600V, Cat. III |
| Influence of Adjacent Conductor |
<0.2mA/AAC |
| Influence of Conductor Position |
0.02% of Reading @ 50/60Hz |
| Influence of Frequency |
| Range |
1mV/A, 10mV/A |
| Range Value |
10 to 1000Hz, 1 to 10kHz, 10 to 50kHz, 50 to 100kHz, 10 to 1000Hz, 1 to 10kHz |
| Range |
10mV/A, 100mV/A |
| Influence of Humidity |
10 to 90%: £0.1% |
| Output Signal |
| Range Value |
1mV/A, 10mV/A, 100mV/A |
| Output Signal |
1A to 2000A peak, 0.1A to 200A peak, 10mA to 20A peak |
| Accuracy |
| Current Range |
1mV/A (1V at 1000A), 10mV/A (1V at 100A), 100mV/A (1V at 10Arms) |
| Accuracy |
Per IEC 185-26-27 |
| Mechanical Specifications |
| Altitude |
Operating: 0 to 2000m; Non-operating: 0 to 12Km |
| Colors |
Dark gray handles with red jaws |
| Dimensions |
4.37 x 8.50 x 1.77" (111 x 216 x 45mm) |
| Drop Test |
1m (IEC 68-2-32) |
| Jaw Opening |
2.25" (57mm) max |
| Material |
Handles: Polycarbonate +ABS Gray: UL 94 V0; Jaws: Polycarbonate, Red: UL 94 V0 |
| Maximum Bus Bar Size |
1.95 x 0.19" (50 x 5mm) |
| Maximum Cable Diameter |
2.05" (52mm) |
| Mechanical Shock |
100g (IEC 68-2-27) |
| Operating Temperature |
14° to 122°F (-10° to 50°C) |
| Operating Relative Humidity |
0 to 85% @ 35°C |
| Output |
6 ft (2m) insulated lead with insulated BNC Connector |
| Protection Index (IP) |
IP 40 (IEC 529) |
| Impact Test |
IK04 0.5 J EN50102 |
| Storage Temperature |
-4° to 158°F (-20° to 70°C) |
| Vibration |
Test per IEC 68-2-6 |
| Vibration |
| Range Value |
5 to 15Hz, 15 to 25Hz, 25 to 55Hz |
| Vibration |
Amplitude: 0.15 mm per IEC 68-2-6, Amplitude: 1 mm per IEC 68-2-6 Amplitude : 0.25 mm per IEC 68-2-6 |
| Weight |
1.21 lbs (550g) |
| External Influences |
| Influence of Temperature |
£0.15% per 10K° |
| Safety Reference Specifications |
| Safety Ratings |
EN 61010-2-32 |
| Agency Approvals |
CE Mark |
| Unique Features |
Max size conductor 2.05". BNC connector |
| Warranty |
12 MONTHS (1 YEARS) |
| Calibration Included |
Factory Calibration |
| Data Logging |
No |
| Shipping Weight |
3 LBS |
| ECCN Number |
EAR99 |
| Country of Origin |
United States |
|