AEMC C.A 6116N Kit
Catalog #: 2138.10
Multi-Function Installation Tester Model C.A 6116N Kit (US) {includes C177A, DataView Software}
- Overview
- Specifications
- Accessories
Product Highlights
- Includes C177A, DataView Software
- Testing according to the international standards: IEC 60364-6, NF C 15-100, VDE 100, XP C 16-600, etc.
- Simple, reliable connection thanks to the contextual help for each function, including all the connection diagrams
- Suitable for all neutral systems (TT, TN, IT)
- Type-B RCD testing available
- Integrated fuse table for quick reading of the results on the instrument
- Li-Ion battery for a longer battery life
- Measurements: voltage, current via clamp, power, waveforms and harmonics.
- Measurement of voltage drop for correct sizing of conductor diameters
- Loop measurement with 1 mΩ resolution
- 3-level storage
Each Unit Includes
- C177A
- Tester delivered with a carrying bag
- 1 type-2 mains power pack / charger
- 1 Li-Ion battery pack
- 1 USB A/B cable, 1.80 m, with ferrite
- 1 three-point cable - 3 safety leads (red, blue and green)
- 3 test probes, Ø 4 mm (red, blue and green)
- 3 crocodile clips (red, blue and green)
- 2 elbowed-straight safety leads 3 m (red and black)
- 1 three-point Euro mains cable
- 1 x 2P EURO mains cable
- 1 remote-control probe
- 1 wrist strap
- 1 scratch-proof film mounted on the instrument
- 1 x 4-point hands-free strap
- ICT data export software on CD-ROM
- 6 operating manuals on C (one per language)
- 1 safety datasheet in 20 languages
- 1 tester delivered in a carrying bag with PA 30 W power pack
- 1 three-point cable - 3 safety leads (red, blue and green)
- 3 test probes, Ø 4 mm (red, blue and green)
- 3 crocodile clips (red, blue and green)
- 2 elbowed-straight safety leads (red and black) 3 m long
- 1 three-point Euro mains cable
- 1 remote-control probe
- 1 scratch-proof film mounted on the instrument
- 1 wrist strap
- 1 x 4-point hands-free strap
- 6 operating manuals on CD
- 1 safety datasheet in 20 languages
Technical Specifications |
|
C.A 6113 |
C.A 6116N |
C.A 6117 |
Continuity / Resistance |
I rated / Range / Resolution |
I > 200 mA / 39.99 Ω/ 0.01Ω / ± (1.5% of measurement + 2 cts) 12 mA / 39.99 Ω & 399.9 Ω / 0.01 & 0.1 Ω /± (1.5% of measurement + 5 cts) with beep |
Range / Resolution / Accuracy |
4 kΩ/ 1 Ω / ±(1.5 % of measurement + 5 cts) 40 kΩ - 400 kΩ/ 10 Ω - 100 Ω / ±(1.5 % of measurement + 2 cts) |
Insulation |
Rated voltage |
Utest: 50 /100 / 250 / 500 / 1,000 V DC |
Range / Resolution / Accuracy |
0.01 MΩ to 2 GΩ / 10 kΩ to 1 MΩ / ±(5 % of measurement + 3 cts) |
Short-circuit current |
≤ 3 mA |
Earth |
3P EARTH Range / Resolution / Accuracy |
0.50 Ω to 40 Ω/ 0.01 Ω / ±(2 % of measurement + 10 cts) 40 Ω to 15 kΩ / 0.1 Ω to 1 Ω / ±(2 % of measurement + 2 cts) 15 kΩ to 40 kΩ / 10 Ω/ ±(10 % of measurement + 2 cts) |
Others |
Measurement of resistance of auxiliary stakes RH & RS (up to 40 kΩ) |
Ufk |
Complies with SEV 3569 |
1P SELECTIVE EARTH Range / Resolution / Accuracy |
0.20 Ω to 39.99 Ω - 40 Ω to 399.9 Ω / 0.01 Ω - 0.1 Ω / ±(10 % of measurement + 10 cts) (ISel via clamp) |
Loop Impedance (Zs (L-PE) and Zi (L-N or L-L)) - 1P Live Earth |
Live Earth Installation voltage / Freq. |
90 to 500 V / 15.8 to 17.5 Hz - 45 to 65 Hz |
High-current mode with TRIP Zs (L-PE) & Zi (L-N or L-L) Range / Resolution / Accuracy |
Max. test current: 7.5 A (0.050) 0.100 Ω to 0.5 Ω / 0.001 Ω/ ±(10% of measurement + 20 cts) • 0.5 Ω to 3.999 Ω / 0.001 Ω/ ±(5 % of measurement + 20 cts) 3.999 to 39.99 Ω/ 0.01Ω / ±(5% of measurement + 2 cts) • 39.99 Ω to 399.99 Ω / 0.1 Ω/ ±(5 % of measurement + 2 cts) |
NO TRIP mode (Zs (L-PE) only) |
Test current: 6 mA - 9 mA - 12 mA (as required) 0.20 Ω to 0.99 Ω / 0.01 Ω / ±(15 % of measurement + 10 cts) 1.00 to 1.99 Ω / 0.01 Ω / ±(15 % of measurement + 3 cts) 2.00 to 39.99 Ω / 0.01 Ω / ±(10 % of measurement + 3 cts) 40.00 Ω to 399.9 Ω / 0.1 Ω / ±(5 % of measurement + 2 cts) 400 to 3999 Ω / 1 Ω / ±(5 % of measurement + 2 cts) |
Calculation of Ik short-circuit current (PFC (Zs)), I Sc PSCC (Zi) |
Fault current and short-circuit current: 0.1 A to 20 kA |
Integrated fuse table |
- |
Yes |
Voltage drop ΔV%(Zi) |
- |
-40 % to + 40 % |
Others |
Measurement of the resistive and inductive components of the Zs and Zi impedances |
AC and A-type RCDs |
Installation voltage / Frequency |
90 V to 500 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz |
IΔn |
10/30/100/300/500/650/1,000 mA (90 V - 280 V) or variable - 10/30/100/300/500 mA (280-550 V) or variable Ramp and pulse test |
No-trip test |
at ½ IΔn - Duration: 1,000 ms or 2,000 ms |
Ramp mode |
0.2 to 0.5 x IΔn (Uf) / 0.3 x IΔn to 1.06 x IΔn in increments of 3.3 % x IΔn |
Trip time measurement: Range / Resolution / Accuracy |
0.2 to 0.5 x IΔn (Uf) / 0.5 x IΔn / 2 x IΔn (selective) / 5 x IΔn Pulse: 0 to 500 ms / 0.1 and 1 ms / 2 ms, Ramp mode: 0 to 200 ms / 0.1 ms / 2 ms |
B-type RCDs |
Installation voltage / Frequency |
- |
90 V to 275 V / 15.8 Hz to 17.5 Hz and 45 Hz to 65 Hz |
IΔn: ramp / pulse 2 x IΔn pulse 4 x IΔn |
- |
10/30/100/300/500 mA
10/30/100 mA with pulse 4 IΔn
Duration: 150 ms with 4 x IΔn or 300 ms with 2 x IΔn |
Test in ramp mode |
- |
0.2 x IΔn to 2.2 x IΔn |
Trip test:
2 x IΔn
4 x IΔn |
- |
IΔN ≤ 200 mA: 2.2 x 2 x IΔn
IΔN > 200 mA: 1.1 x 2 x IΔn
IΔN ≤ 100 mA: 2.2 x 4 IΔN |
Other Measurements |
Current by clamps C177/C177A |
(0.5 mA*) 5 mA to 19.99 A (C177) / 20 mA to 199.9 A (C177A) |
5.0 mA to 199.9 A (C177A) |
Current by clamp MN77 |
(1 mA*) 5.0 mA to 19.99 A |
Voltage |
0 to 550 VAC/DC / DC and 15.8 to 500 Hz |
Frequency |
10 to 500 Hz |
Phase rotation |
20 to 500 VAC |
Active power |
- |
0 to 110 kW single-phase - 0 to 330 kW three-phase Simultaneous display of voltage and current waveforms |
Harmonics |
- |
Voltage and current / up to 50th order / THD-F /THD-R |
General Specifications |
Display |
Large 5.7" backlit graphic monochrome LCD screen, 320 x 240 points |
Large 5.7" backlit graphic colour LCD screen, 320 x 240 points |
Storage/Communication |
- |
via USB for data transfer and report creation |
Power supply: rechargeable battery |
NiMH 9.6 V rated 4 Ah |
Lithium-ion 10.8 V rated 5.8 Ah |
Battery life |
up to 24 hours |
up to 30 hours |
Dimensions / weight |
280 x 190 x 128 mm / 2.2 kg |
Protection |
IP 53 / IK04 |
EMC |
IEC 61326-1 |
Electrical safety |
IEC 61010 -1 - 600 V CAT III - 300 V CAT IV - IEC 61557 |
|
Accessories
Product |
Price |
|
AEMC 2135.35
Catalog #: 2135.35
Test Kit for 3-Point Testing, Kit (Carrying Bag, [2] 150 ft Color-coded Leads on Spools (Red/Blue), [1] 30 ft Lead (Green), [2] 5 ft Color-coded Leads (Red/Blue), [2] 14.5" T-shaped Auxiliary Ground Electrodes, [1] Set of 5, Spaded Lugs and [1] 100 ft AEMC Tape Measure)
|
$580.23
|
|
AEMC 2135.36
Catalog #: 2135.36
Test Kit for 4-Point Testing, Kit (Carrying Bag, [2] 300 ft Color-coded Leads on Spools (Red/Blue), [2] 100 ft Color-coded Leads (hand tied-Green/Black), [2] 5 ft Color-coded Leads (Red/Blue), [4] 14.5" T-shaped Auxiliary Ground Electrodes, [1] Set of 5, Spaded Lugs and [1] 100 ft AEMC Tape Measure)
|
$720.23
|
|
AEMC 2136.80
Catalog #: 2136.80
Cable - Replacement USB Cable, 10ft for Models 8510, 8335 & C.A 6116
|
$40.23
|
|
AEMC 2140.19
Catalog #: 2140.19
Battery Replacement 9.6V NiMH Rechargeable for Models 3945/3945-B, 6550, 6555, 8333, 8335, 8336, 8435, OX Series, and C.A 6116
|
$200.23
|
|
AEMC 2155.75
Catalog #: 2155.75
Megohmmeter Test Probe {for use with Models 6522-6536, 6116N, 61117, 600V CAT IV}
|
$199.21
|
|
AEMC 2960.47
Catalog #: 2960.47
Battery Replacement 5.8AH 64Wh Li-Ion Battery Pack for Models C.A 6116N and C.A 6117
|
$269.21
|
|
AEMC 5000.19
Catalog #: 5000.19
Adapter Replacement Power Adapter 110V/230V with US Power Cord for use with Models 8333, 8335, 8336, PEL 105, and C.A 6116
|
$172.21
|
|
AEMC 5000.73
Catalog #: 5000.73
Adapter Power Adapter 110/230V w/US Power Cord for use with Models C.A 6116N And C.A 6117
|
$0.00
|
|
|
|